MTL5523V–VL Solenoid/Alarm driver with voltage control
MTL5523V – VL Solenoid/Alarm driver with voltage control
MTL5523V product specification as below
MTL5523V–VL Solenoid/Alarm driver with voltage control
With the MTLx523V/VL interface, an on/off
device in a hazardous area can be controlled by a voltage signal in the safe
area. It is suitable for driving loads such as solenoids. Line fault detection
(LFD), which operates irrespective of the output state, is signalled by a
safe-area solid-state switch which energises if a field line is open or short– circuited.
Earth fault detection can be provided by connecting an MTL4220 earth leakage
detector to terminal 3.
SPECIFICATION
MTL5523V–VL Solenoid/Alarm driver with voltage control
See also common specification
Number of channelsOne
Location of load
Zone 0, IIC, T4–6 hazardous area if suitably
certified
Div. 1, Group A, hazardous location
Hazardous-area
output (MTLx523V)
Minimum
output voltage: 13.6V at 48mA
Maximum
output voltage: 24V from 180Ω
Maximum
off-state output voltage: 4V from 180Ω
Current
limit: 48mA minimum
Hazardous-area
output (MTLx523VL)
Minimum
output voltage: 11.1V at 48mA
Maximum
output voltage: 24V from 232Ω
Maximum
off-state output voltage: 4V from 232Ω
Current
limit: 48mA minimum
Output
ripple
< 0.5%
of maximum output, peak to peak
Control
input
Suitable
for 24V logic drive
Output
turns on if > 18V applied across control input
Output
turns off if < 5V applied across control input
Maximum control
input voltage: 28V
Maximum
control system output leakage current: 0.5mA
Response
time
Output
within 10% of final value within 100ms
Line fault
detection (LFD)
Open or
short circuit in field cabling energises solid state
line-fault
signal.
LFD transistor
is switched off, provided that the field circuit impedance is >
55Ω and
< 4kΩ.
Line fault
signal characteristics
Maximum
off-state voltage: 35V
Maximum
off-state leakage current: 10µA
Maximum
on-state voltage drop: 2V
Maximum
on-state current: 50mA
LED
indicators
Green:
power indication
Yellow:
output status, on when output active
Red: LFD
indication, on when line fault detected
Maximum
current consumption
100mA at
24V dc
Power
dissipation within unit
1.2W with
typical solenoid valve, output on
2.0W worst
case
Safety
description (MTLx523V)
Vo=25V
Io=147mA Po= 0.92W Um = 253V rms or dc
Safety
description (MTLx523VL)
Vo=25V
Io=108mA Po= 0.68W Um = 253V rms or dc
Other related models for 5523V as below for your reference.
MTL5523V–VL Solenoid/Alarm driver with voltage control
MTL5018AC
MTL5501-SR
MTL5510
MTL5510B
MTL5511
MTL5513
MTL5514
MTL5514D
MTL5516C
MTL5517
MTL5521
MTL5522
MTL5523
MTL5523V – V
MTL5524
MTL5525
MTL5526
MTL5541
MTL5541A
MTL5541AS
MTL5541S
MTL5544
MTL5544A
MTL5544AS
MTL5544D
MTL5544S
MTL5546
MTL5546Y
MTL5549
MTL5549Y
MTL5573
MTL5575
MTL5576-RTD
MTL5576-THC
MTL5581
MTL5582
MTL5582B
MTL5991
MTL5531
MTL5532
MTL5533
MTL5561
MPA5500
MTL5051
MTL5053
MTL5314
MTL5599
MTL5523V–VL Solenoid/Alarm driver with voltage control
If you have any other question about MTL5523V, please feel free to contact me here!
Contact details
HONGKONG XIEYUAN TECH CO., LIMITED
Telephone:86-
Mobile :86-(Whatapp&Wechat
is available)
Skype:xyautomation
E-mail:sales1@hkxytech.com
Leave a message for product
- 温馨提示:为规避购买风险,建议您在购买前务必确认供应商资质与产品质量。
- 免责申明:以上内容为注册会员自行发布,若信息的真实性、合法性存在争议,平台将会监督协助处理,欢迎举报