Yokogawa Analog Input Module AAI143-S53
Manufacturer: Yokogawa Electric Corporation
Control System: CENTUM VP
STANDARD SPECIFICATIONS
Current Input Modules (Isolated)
This module inputs 4 to 20 mA.
It can be used in dual redundant configuration.
Yokogawa Analog Input Module AAI143-S53
Items
|
Specifications
|
Model
|
AAI143 (*1)
|
Number of input channels
|
16, isolated
|
Input signal
|
4 to 20 mA
|
Allowable input current
|
24 mA
|
Withstanding voltage
|
Between input and system:
1500 V AC For 1 minute (*4)
|
Input resistance
|
Power ON
|
270 Ω (20 mA) to 350 Ω (4 mA)
(*2)
|
Power OFF
|
500 kΩ or more
|
Accuracy
|
±16 μA
|
Data update period
|
10 ms
|
Transmitter power supply
|
19.0 V or more (at 20 mA)
25.5 V or less (at 0 mA) (output current limit: 25 mA) (*5)
|
Setting of 2-wire or 4-wire
transmitter
|
For each channel by setting
pin
|
Drift due to ambient
temperature change
|
±16 μA/10˚C
|
Maximum current consumption
|
230 mA (5 V DC) , 540 mA (24
V DC)
|
Weight
|
0.3 kg
|
External communication
|
Pressure clamp terminal, MIL
connector cable, Dedicated cable (KS1)
|
HART communication (*3)
|
Available
|
*1: This module Yokogawa Analog Input Module
AAI143-HE3 does not allow a Zener barrier to be connected. If the module
is to be used in intrinsically safe applications, use an isolation barrier.
*2: Viewed from the terminals, module input resistance is, depending
on the current flowing:
250 Ω +( voltage
drop (0.4 V maximum) in the input protection circuit)/(current
value)
*3: When installing the module Yokogawa Analog Input Module
AAI143-HE3 with HART function to a remote node, the firmware of EB401 must
be Rev 2 or later.For HART function specifications, refer to “HART
Communication Package (for A□I□□□-H) (GS 33Q03L70-31E).”
*4: The withstanding voltage for using the dedicated cable is 500 V
AC (between the input signal and the system).The withstanding voltage for using
MIL connector cable depends on the electrical specifications of its cable.
*5: This voltage is developed between connecting terminals for
this Yokogawa Analog Input Module AAI143-S53 module’s 2-wire transmitter.
When calculating if transmitter minimum operating voltage requirement will be
satisfied, remember to allow for voltage drop in external wiring.
MODELS AND SUFFIX CODES
Yokogawa Analog Input ModuleAAI143-S53
|
|
Description
|
Model
|
AAI143
|
Analog Input Module (4 to 20
mA, 16-channel, Isolated)
|
Suffix Codes
|
-S
|
Standard type
|
-H
|
With digital communication
(HART protocol)
|
5
|
With no explosion protection
|
E
|
With explosion protection
|
0
|
Basic type
|
3
|
With ISA Standard G3 option
and temperature (-20 to 70 °C) option
|
Option Codes
|
/K4A00
|
With KS Cable Interface
Adapter (For connecting AEA4D Terminal Board) [Model: ATK4A-00]
|
/A4S00
|
With Pressure Clamp Terminal
Block [Model: ATA4S-00]
|
/A4S10
|
With Pressure Clamp Terminal
Block (surge absorber) [Model: ATA4S-10]
|
/A4D00
|
With Dual Pressure Clamp
Terminal Block [Model: ATA4D-00]
|
/A4D10
|
With Dual Pressure Clamp
Terminal Block (surge absorber) [Model: ATA4D-10]
|
/CCC01
|
With Connector Cover for MIL
Cable [Model: ACCC01]
|
YOKOGAWA AAI143-S53 Analog Input Module
Selected Model
AAI143-S50/K4A00, AAI143-S50/A4S00, AAI143-S50/A4S10,
AAI143-S50/A4D00, AAI143-S50/A4D10, AAI143-S50/CCC01,
AAI143-S53/K4A00, AAI143-S53/A4S00, AAI143-S53/A4S10,
AAI143-S53/A4D00, AAI143-S53/A4D10, AAI143-S53/CCC01,
AAI143-SE0/K4A00, AAI143-SE0/A4S00, AAI143-SE0/A4S10,
AAI143-SE0/A4D00, AAI143-SE0/A4D10, AAI143-SE0/CCC01,
AAI143-SE3/K4A00, AAI143-SE3/A4S00, AAI143-SE3/A4S10,
AAI143-SE3/A4D00, AAI143-S53/A4D10, AAI143-S53/CCC01,
AAI143-H50/K4A00, AAI143-H50/A4S00, AAI143-H50/A4S10,
AAI143-H50/A4D00, AAI143-h50/A4D10, AAI143-H50/CCC01,
AAI143-H53/K4A00, AAI143-H53/A4S00, AAI143-H53/A4S10,
AAI143-H53/A4D00, AAI143-h53/A4D10, AAI143-H53/CCC01, AAI143-HE0/K4A00, AAI143-HE0/A4S00,
AAI143-HE0/A4S10, AAI143-HE0/A4D00, AAI143-HE0/A4D10, AAI143-HE0/CCC01,
AAI143-HE3/K4A00, AAI143-HE3/A4S00, AAI143-HE3/A4S10,
AAI143-HE3/A4D00, AAI143-HE3/A4D10, AAI143-HE3/CCC01