MTL safety barriers MTL5032 Pulse Isolator
MTL safety barriers MTL5032 Pulse Isolator
MTL safety barriers MTL5032 Pulse Isolator
Feature
The MTL5032 isolates pulses from a switch, proximity detector, current pulse transmitter or voltage pulse transmitter located in a hazardous area.
MTL safety barriers MTL5032 Pulse Isolator
Specification
Number of channels
One
Location of switch
Zone 0, IIC, T6 hazardous area
Div. 1, Group A hazardous location
Location of proximity detector or transmitter
Zone 0, IIC, T4–6 hazardous area if suitably certified
Div. 1, Group A hazardous location
Safe-area output
Maximum off-state values: V = 35V, I = 10µA
Maximum on-state current: 50mA
Voltage drop: [1 + (0.1 x current in mA)] V
Output off if supply fails
Hazardous-area input
Switch: output-on (off) if switch closed (open)
Proximity detector: meets NAMUR and DIN 19234 standards
Pulse (I): Supply 16.5V dc at 20mA,
Short-circuit current 24mA
Output on (off) >8.9mA (<6.8mA)
Switching hysteresis: 0.5mA typical
Pulse (V): Input impedance >10kΩ
Switching point voltage (Vsp): 3, 6 or 12V
(selectable)
Output on (off) if input >1.2 x Vsp (<0.8 x Vsp)
Switching hysteresis: 0.11 x Vsp typical
Pulse width
High: 10µs minimum
Low: 10µs minimum
Frequency range
0 to 50kHz