Pepperl Fuchs RTD Converter KFD0-TR-Ex1


Pepperl Fuchs RTD Converter KFD0-TR-Ex1


Pepperl Fuchs RTD Converter KFD0-TR-Ex1

Pepperl Fuchs RTD Converter KFD0-TR-Ex1


Feature

1-channel isolated barrier
24 V DC supply (loop powered)
2- or 3-wire Pt100 RTD input
Output 4 mA ... 20 mA, temperature linearization selectable
DIP switch selectable ranges
Sensor breakage detection

Pepperl Fuchs RTD Converter KFD0-TR-Ex1

Function

This isolated barrier is used for intrinsic safety applications. It is a loop-powered isolator that converts the resistance from a 3-wire RTD in the
hazardous area to a 4 mA ... 20mA signal in the safe area.
A selectable analog linearization ensures a temperature linear 4 mA ... 20mA output between 25 °C ... 375 °C.
It also features conveniently located DIP switches, rotary switches and potentiometers to make field calibration easy.

Pepperl Fuchs RTD Converter KFD0-TR-Ex1

Assembly

Pepperl Fuchs RTD Converter KFD0-TR-Ex1