Pepperl Fuchs SMART Transmitter Power Supply HiD2030

Pepperl Fuchs SMART Transmitter Power Supply HiD2030
·2-channel isolated barrier
·24 V DC supply (bus powered)
·2-wire SMART transmitters or current sources
·Usable as signal splitter (1 input and 2 outputs)
·Dual output 4 mA ... 20 mA or 1 V ... 5 V
·Line fault detection (LFD)
·Up to SIL 2 acc. to IEC 61508
Pepperl Fuchs SMART Transmitter Power Supply HiD2030
Function
This isolated barrier is used for intrinsic safety applications. It provides a fully floating supply to power 2-wire SMART transmitters in the hazardous
area, and repeats the current to drive a safe area load. It is also used with 2-wire current sources.
Digital signals may be superimposed on the analog values in the hazardous or safe area, which are transferred bidirectionally.
A separate fault output on the bus is signaled if the input signal is outside the range 0.2 mA ... 24 mA. The fault conditions can be monitored via a
Fault Indication Board.
This module mounts on a HiD Termination Board. Pepperl Fuchs SMART Transmitter Power Supply HiD2030
Application
The device supports the following SMART protocols:
• HART
• BRAIN
• Bailey (only STT02 communication, e. g. BCN series)
• Foxboro
Configuration
Configure the device in the following way:
• Push the red Quick Lok Bars on each side of the device in the upper position.
• Remove the device from Termination Board.
• Set the DIP switches according to the figure
Pepperl Fuchs SMART Transmitter Power Supply HiD2030