The TView is the build-in type touch screen withthe build-in & low power-consumption CPU as the core, andapplies in the building automation industry. The product adopts the7-inch high-brightness TFT LCD; the true-color displayingresolution can be up to 800 x 600 pixels. It can insert theconfiguration software (runtime) to apply in the field control ofthe control system, and is convenient & reliable.
n Product Specification
Structure: IndustrialPlastic
Mounting Type:Build-in
Power Supply: DC24V30W
Overall Dimension: 226.5mm x163mm x 36mm
Front Panel: 226.5mm x 163mm x6mm
Panel View-port: 153.6mm x86.6mm
Shell Outline: 213mm x 150mm x30mm
Cabinet Opening: 215mm x152mm
Shell Color: Grey
n Product Properties
l LCD: 7.5-inch FFT LCD, Resolution (800 * 600)
l CPU: Basic Frequency 400MHz
l Touch Screen: Four Wire Resistive
l Memory: 64M SDRAM
l Storage Device: 64M FLASH
l Interface: RS232, TR232/485, USB
n Technical Specification
Size: 7-inch
LCD: TFT LCD, LEDBacklight
Display Color: TrueColor
Resolution: 800 *480
Touch Screen:Resistive
Power Supply: 24VDC
CPU Mainboard: ARMLow-consumption, 400MHz
Memory: 64M SDRAM
Storage Device: 64MFLASH
Working Temperature:0-45°C
Working Humidity:10%-90%RH
Storage Temperature:-10-55°C
USB Interface: One Master, OneSlave
Serial Interface: One LoopRS232, One Loop RS485
Ethernet: RJ45 EthernetInterface
Certification: CE,FCC
BACnet Support: Conformsto the Advanced Application Controller (B-ASC) Standard DeviceProfile as defined,see the PICS.
Communication: Thefollowing ports are available on the BFC controlmodules:
EIA-485 port for MS/TP (9600 bps– 76.8 kbps).
Rnet Port supports:
1. Local access for systemstart-up and troubleshooting.
2. Local operator interfaceSIMView or TView.
3. RS Room Sensors - averagingor high/low select control.
Binary Outputs: 24VAC50/60HZ
UniversalInputs:
Supported input types include:0-5 V-dc, 0-10 V-dc, 4-20 mA, Thermistor (10k Ohm Type II), 1kOhmRTD (Platinum, Nickel or Balco), and Dry Contact.
Memory: 1 MBytenon-volatile battery-backed RAM, 1 MByte Flash memory, 16-bitmemory bus. (Shelf life of the battery is 10 years with 10,000hours of continuous operation.)
Real-time Clock:Battery-backed real-time clock.
Status Indicators: LEDstatus indicators for EIA-485 communication, running, error, powerand all digital outputs.
Module Addressing: Rotarydip switches for intuitive network addressing ofmodules.
Protection: Built-insurge and transient protection circuitry for power, communications,inputs and outputs.
Listed by: CE, EMC GB/T17626
Environmental Operating Range:-20ºF to 140ºF (-29ºC to 60ºC); 10 to 90% relative humidity,non-condensing.
NOTE: Control modulesshould be mounted in protective enclosures.
Power Requirements: 24 V-ac ±10%, 26 V-dc (25 V min, 30 V max), 50 to 60Hz, 20VA.
NOTE: Power consumptionwill increase when SIMViewor other accessories areattached.
Physical: Rugged aluminumcover. Removable screw terminalblocks.